The BA (Building Automation) Application Controller is ideal for WAGO flexROOM® applications and is used in WAGO 2854 flexROOM® distribution boxes.
The flexROOM® applications performed via Application Controller are divided into function groups (FG). These applications can only be performed by a controller if the application's FG is less than or identical to the controller's FG. The controller is delivered without preloaded application.
In conjunction with the WAGO-I/O-SYSTEM, the Application Controller can also be used as a programmable controller within ETHERNET networks.
Two ETHERNET interfaces and an integrated switch allow the fieldbus to be wired in a line topology. This eliminates additional network devices, such as switches or hubs. Both interfaces support Auto-Negotiation and Auto-MDI(X).
The DIP switch configures the last byte of the IP address and may be used for IP address assignment.
The PLC supports both MODBUS/TCP and EtherNet/IP. It also supports a wide variety of standard ETHERNET protocols for easy integration into IT environments (e.g., HTTP, BootP, DHCP, DNS, SNTP, SNMP, FTP).
An integrated Web server provides configuration options to the user, while displaying PLC status information. The IEC 61131-3 programmable controller is multitasking-capable and features a battery-backed RTC.
A data memory of 1 MB is available.
The 750-884 PLC has a slot for a removable memory card, allowing device parameters or files (e.g., boot files) to be transferred from one controller to another. The memory card can be accessed via FTP and be used as an additional drive.
- Ethernet
- Ethernet/IP
- Modbus